Chapter 4

Installation

4-10

Figure 4.10

Typical Analog Output Connections

+

TB3

Analog Output

Com

0 to

±

10VDC

1mA maximum

TB4

Connect shield to drive end

only. Other end is to be

insulated and left floating.

Figure 4.11

Typical Digital Output Connections

45

TB3

46

Digital

Output #1

43

44

Digital

Output #2

Dry Contacts 0.6A @ 125VAC