Chapter 8

Parameter Table

8-13

Parameter 558 - [A> Digital Out 1]

508 - [B> Digital Out 1]

Use: Maps Digital Output 1
Program Terminal Units: None
Maximum Value: 15
Minimum Value: 0
Default Value: 10

Description: This parameter has a range of 0 to 15. It establishes which bit
of Discrete Output parameter 450/350 controls the Output 1 relay. When
the bit is set the relay contact closes. The default value for this parameter is
10 which is the bit corresponding to “At Zero Speed” when parameter
450/350 is linked to Logic Status.

Parameter 559 - [A> Digital Out 2]

509 - [B> Digital Out 2]

Use: Maps Digital Output 2
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 15
Default Value: 5

Description: This parameter has a range of 0 to 15. It establishes which bit
of Discrete Output parameter 450/350 controls the Output 2 relay. When
the bit is set the relay contact closes. The default value for this parameter is
5 which is the bit corresponding to “Drive Running” when parameter
450/350 is linked to Logic Status.

Parameter 575 - [A> DAC Scale 1]

525 - [B> DAC Scale 1]

Use: Scale Factor for Analog Output 1
Program Terminal Units: None
Minimum Value: –1
Maximum Value: +1
Default Value: +1

Description: This parameter determines the scale factor or Gain for
Analog Output 1. A

±

32767 digital value from the Drive is converted to a

±

10V DC signal. Before the digital value is converted the Scale Factor is

applied, thus allowing an effective digital range of

±

2048 (32767/16 =

2048 = 10V DC ). This is achieved by programming the Scale Factor to
.0625 or 1/16.