Chapter 8

Parameter Table

8-17

Parameter 585 - [A> Digital In 3]

535 - [B> Digital In 3]

Use: Maps Digital Input 3
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 15
Default Value: 12

Description: This parameter has a range of 0 to 15. It establishes which bit
of the Digital Input parameter is affected by Digital Input 3. Connecting
Digital Input 3 (Terminal TB3 – 50) to Digital Common (TB3 – 47) will
cause the bit specified by this parameter to be set to 1. Removing the
connection will cause the specified bit to be set to 0. The default value for
this parameter is 12 which is the bit corresponding to START when the
Digital Input parameter is linked to Logic Command.

Parameter 586 - [A> Digital In 4]

536 - [B> Digital In 4]

Use: Maps Digital Input 4
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 15
Default Value: 14

Description: This parameter has a range of 0 to 15. It establishes which bit
of the Digital Input parameter is affected by Digital Input 4. Connecting
Digital Input 4 (Terminal TB3 – 51) to Digital Common (TB3 – 47) will
cause the bit specified by this parameter to be set to 1. Removing the
connection will cause the specified bit to be set to 0. The default value for
this parameter is 14 which is the bit corresponding to CLEAR FAULTS
when the Digital Input parameter is linked to Logic Command.

Parameter 599 - [A> DS: VERSION]

549 - [B> DS: VERSION]

Use: Adapter card identifier
Program Terminal Units: None

Description: This parameter identifies the Adapter card type and firmware
version number.