Chapter 8

Parameter Table

8-16

Parameter 582 - [A> DAC Offset 4]

532 - [B> DAC Offset 4]

Use: Offset for Analog Output 4
Program Terminal Units: Volts
Minimum Value: –20V DC
Maximum Value: +20V DC
Default Value: 0V DC

Description: This parameter determines the offset applied to the raw
Analog Output 4 value after the Scale Factor is applied. This allows the
User to shift the range of his analog output.

Parameter 583 - [A> Digital In 1]

533 - [B> Digital In 1]

Use: Maps Digital Input 1
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 15
Default Value: 11

Description: This parameter establishes which bit of the Digital Input
parameter is affected by Digital Input 1. Digital Input 1 is designed for use
with Normally Closed operator devices. Connecting Digital Input 1
(Terminal TB3 – 48) to Digital Common (Terminal TB3 – 47) will cause
the bit specified by this parameter to be set to 0. Removing the connection
will cause the bit to be set to 1. The default value for this parameter is 11
which is the bit corresponding to STOP when the Digital Input parameter is
linked to Logic Command.

Parameter 584 - [A> Digital In 2]

534 - [B> Digital In 2]

Use: Maps Digital Input 2
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 15
Default Value: 9

Description: This parameter has a range of 0 to 15. It establishes which bit
of the Digital Input parameter is affected by Digital Input 2. Connecting
Digital Input 2 (Terminal TB3 – 49) to Digital Common (Terminal
TB3 – 47) will cause the bit specified by this parameter to be set to 1.
Removing the connection will cause the bit to be set to 0. The default value
for this parameter is 9 which is the bit corresponding to JOG2 when the
Digital Input parameter is linked to Logic Command.