Rockwell Automation 1395 Discrete Adapter, Rev 3.XX-8.XX User Manual

Page 31

Advertising
background image

Chapter 5

StartĆUp

5-8

As shown in Figure 5.5, another 0 to 10V DC meter is connected to
Digital-To-Analog (D/A) output number 2. In this example, Parameter 452
which feeds the D/A is linked to drive Parameter 112, Armature Current
Feedback. In this example we assume that armature Current Feedback will
vary between 0% and 200% rated current. This means the drive digital
signal will vary between 0 and 8192 and the D/A signal must vary between
0 and 2048 for a 0 to 10V DC output. In this case, programming Parameter
577 to a value of 0.25 will provide the correct scaling
(0.25 x 8192 = 2048). Setup Parameter 578 can remain at zero volts offset
because a DC offset is not required in this example (Refer to Figure 5.5).

Figure 5.5

Example 2: Analog Output

0 to 200% Current Indication

Scale

A

D

0

4096 = 100%

or 1 per unit

Example 2:

0.25

0

100%

200%

0V

10V

Offset

0

+8192

0

+2048

0

+2048

0

-2048

Analog Range

Digital Range

0 to 200%I

A

0

to 8192

+10V = 200% I

AFDBK

0V = 0% I

AFDBK

0

-10V

+10V

Drive Units

O to 200% IA

After Scaling

After Offset

Meter Voltage

% I

AFDBK

+5V

0
0

0

0

0

+1024

+4096
+1024

+1024

+5V

100%

+2048

+8192
+2048

+2048

+10V

200%