Publication 1403-IN005A-EN-P

6 Product Description

Indicators

Four LED indicators provide information about the operating status of the
card.

Configuration Items

Communication

Table 3 LED Indicators

Label

Name

LED Color

LED State and Communications Condition

RDY

Ready

Red

ON = Control power applied
ON/OFF Flashing = Self-test initialization

LK

Link

Green

ON = UTP (10BaseT) cable properly connected

RX

Receive

Green

ON/OFF Flashing = Receiving Data

TX

Transmit

Green

ON/OFF Flashing = Transmitting Data

Table 4 Communication Configuration Items

Communication Parameter

Description

Range

Default

IP Address Byte a

IP address of this Powermonitor. (Normally in the form
128.1.1.1)

0 to 255

128

IP Address Byte b

1

IP Address Byte c

1

IP Address Byte d

Device ID#

Subnet Mask Byte a

Specifies the subnet mask to apply to the IP address.
Network ID and Host are specified by address class. Zero
bits in the mask indicate bit positions of the host number;
one bits are for subnet ID. (Normally in the form
255.255.255.0)

0 to 255

255

Subnet Mask Byte b

255

Subnet Mask Byte c

255

Subnet Mask Byte d

0

Physical Ethernet Port

Selects the Ethernet media (0=UTP/10BaseT, 1=AUI/
10Base5)

0 = UTP, 1 =AUI

0 = UTP

Keep Alive Time

The maximum allowable time any socket is dedicated to a
connection that is not responding.

5 to 3600 seconds

30

Inactivity Time

The maximum allowable time the entire Ethernet
communication card waits with no network activity
before rebooting.
Set parameter to zero to disable inactivity time.

0 to 1440 minutes
0 = Disabled

30

NOTE

BOOTP, the dynamic acquisition of an IP address, is
enabled when all four address bytes of the programmed IP
address are set to zero. (0.0.0.0)