B-38 Ethernet Communication Card Data Tables

20.25

Display Module No. 2 FRN

0 to 32767

28

0 to 32767

20.26

Display Module No. 3 FRN

0 to 32767

29

0 to 32767

20.27

Auxiliary Frequency

0 to 9999x10

21

30

0 to 9999

31

0 to 32

20.28

Fiber Loop Back Test Results

0 = Fail
1 = Pass

32

0 to 1

20.29

EEPROM Status

33

16-bit Integer

20.30

Device ID

0 to 255

34

0 to 255

20.31

General Purpose Status Bits

bit 0 = oscillograph capture #1
ready to be read
bit 1 = snapshot buffer full
bit 2 = oscillogram capture #1
triggered by a setpoint
bit 3 = oscillograph capture #2
ready to be read
bit 4 = oscillograph capture #2
triggered by setpoint (if clear,
triggered via comms)
(Refer to Note below.)

35

0 to 31

20.32

Block Write Error Status Word
(Block Size ID)

0 = OK
Other value = Error

36

0 to 64

20.33

Block Write Error Status Word
(Parameter Number)

0 = OK
Other value = Error

37

0 to +32767

Reserved Word

38

Reserved Word

39

Table B.30 Diagnostic Data Table (Self-test Results) Read (File N30)

Parameter No.

Parameter Name

Master Module Range

Element

Range

NOTE

Notes for PC application or PLC programmer

Oscillograph triggered via a communication:

Trigger oscillograph capture by writing to the command table.

Check oscillograph data readiness by reading diagnostic table (should be ready almost immediately since
maximum pre-trigger is used for comm port oscillograph requests).

Specify oscillograph channel to read by writing to the command table.

Get oscillograph data by reading oscillograph data table. Subsequent reads return remaining sets of data
for that channel. After the last set of data for that channel, additional reads return data for the next
channel.

Once you have finished collecting all of the data you desire for that capture, release hold of the capture by
writing to the command table. This allows pre-trigger collection of new data and clears the ready
indication in the diagnostic table.

Oscillograph trigger via setpoint:

Trigger oscillograph with a properly configured setpoint.

Check oscillograph data readiness by reading diagnostic table (may have to wait up to 1.2 seconds;
depends on sample rate, number of captures and pre-trigger settings).

Specify oscillograph channel to read by writing to the command table.

Get oscillograph data by reading oscillograph data table. Subsequent reads return remaining sets of data
for that channel. After the last set of data for that channel, additional reads return data for the next
channel. All data for all 7 channels can be retrieved by performing a series of successive reads.

Once you have finished collecting all of the data you desire for that capture, release hold of the capture by
writing to the command table. This allows pre-trigger collection of new data and clears the ready
indication in the diagnostic table.