Even harmonic distortion table, B-25, Harmonic distortion tables - read – Rockwell Automation 1403-NENET Ethernet Communication Card Installation Instructions User Manual

Page 39

Advertising
background image

Publication 1403-IN005A-EN-P

Ethernet Communication Card Data Tables B-25

Harmonic Distortion Tables - Read

Harmonic Distortion Data Tables for Channel 1 through Channel 7 are
identical. There are a total of 14 tables for this information. (V1, V2, V3, I1,
I2, I3, I4) The table sizes indicate this is Harmonic Distortion Data. The
Channel Number designates which one.

Table B.23 Even Harmonic Distortion Table - Channel 1 to 7 Read (File F23)

Parameter No.

Parameter Name

Master Module Range

Element

Range

13.1

IEEE Total Harmonic Distortion

0 to 1000%

1

0 to 1000

13.2

IEC Total Harmonic Distortion

0 to 1000%

2

0 to 1000

13.3

Meets IEEE 519
(Not Available on 1403-LM)

-1 = Unknown
0 = Fail
1 = Pass

3

-1 to +1

13.4

TIF (Not Available on 1403-LM)

0 to 9999x10

21

4

0 to 9999x10

21

13.5

Crest Factor (Not Available on 1403-LM)

0 to 9999x10

21

5

0 to 9999x10

21

13.6

K-Factor (Not Available on 1403-LM)

0 to 9999x10

21

6

0 to 9999x10

21

13.7

Channel Number

1 = L1 Voltage
2 = L1 Current
3 = L2 Voltage
4 = L2 Current
5 = L3 Voltage
6 = L3 Current
7 = L4 Current

7

1 to 7

13.8

Harmonic Distortion - Fundamental ( Not
Available on 1403-LM)

0 to 1000%

8

0 to 1000

13.9

Harmonic Distortion - Second (Not
Available on 1403-LM)

0 to 1000%

9

0 to 1000

13.10

Harmonic Distortion - Fourth ( Not
Available on 1403-LM)

0 to 1000%

10

0 to 1000

13.11

Harmonic Distortion - Sixth (Not
Available on 1403-LM)

0 to 1000%

11

0 to 1000

13.12

Harmonic Distortion - Eighth ( Not
Available on 1403-LM)

0 to 1000%

12

0 to 1000

13.13

Harmonic Distortion - Tenth (Not
Available on 1403-LM)

0 to 1000%

13

0 to 1000

13.14

Harmonic Distortion - Twelfth (Not
Available on 1403-LM)

0 to 1000%

14

0 to 1000

13.15

Harmonic Distortion - Fourteenth ( Not
Available on 1403-LM)

0 to 1000%

15

0 to 1000

13.16

Harmonic Distortion - Sixteenth ( Not
Available on 1403-LM)

0 to 1000%

16

0 to 1000

13.17

Harmonic Distortion - Eighteenth ( Not
Available on 1403-LM)

0 to 1000%

17

0 to 1000

13.18

Harmonic Distortion - Twentieth (Not
Available on 1403-LM)

0 to 1000%

18

0 to 1000

Advertising