Publication 1403-IN005A-EN-P

B-8 Ethernet Communication Card Data Tables

3.12

Present Unit Password

0 to 9999

18

0 to 9999

Reserved

19

Reserved 20

Reserved 21

Reserved

22

(1) See Table B.6 o n pageB-8 for specific command bits to enable these features.

(2) Available on firmware V3.00 or later.

Table B.5 Command Data Table Write (File N13)

Parameter No.

Parameter Name

Master Module Range

Element

Range

Table B.6 Bit Fields for Command Data Table -(Command Word 1)

Command

Bit Location and
Value

Clear Snapshot Log

b0 = 1

Clear Min_Max Log

b1 = 1

Restore Factory Default Configuration

b2 = 1

Clear Hold of Oscillograph Capture #1 (Reserved on 1403-LM)

b3 = 1

Initiate Oscillograph Capture #1 (Reserved on 1403-LM)

b4 = 1

Force Self Test

b5 = 1

Clear Status Input Counter 1

b6 = 1

Clear Status Input Counter 2

b7 = 1

Clear Status Input Counter 3

b8 = 1

Clear Status Input Counter 4

b9 = 1

Clear Battery Usage Timer

b10 = 1

Reserved

b11 = 1

Synchronize Demand Interval

b12 = 1

Clear Hold of Oscillograph Capture #2 (Reserved on 1403-LM)

b13 = 1

Initiate Oscillograph Capture #2 (Reserved on 1403-LM)

b14 = 1

Table B.7 Bit Fields for Command Data Table - (Command Word 2)

Command

Bit Location and
Value

Set Analysis Channel Request (DV1)

b0 = 1

Set Oscillogram Channel Request (DV2)
(Not Available on 1403-LM)

b1 = 1

Set W Hours (DV3)

b2 = 1

Set VAR Hours (DV4)

b3 = 1

Advertising