B-16 Ethernet Communication Card Data Tables

9a.15

Demand kVAR

0 to 9999x10

21

kVAR

18

9a.16

Total True PF

-100 to +100

19

9a.17

kWh net

-9999x10

21

to +9999x10

21

kWh

20

9a.18

kVARh net

-9999x10

21

to +9999x10

21

kVARh

21

9a.19

Number of Records Requested

1 to 265

22

9a.20

Number of Records Read so far

1 to 265

23

9a.21

Record Number Returned

1 to 265

24

9a.22

Internal Identifier

0 to 255

25

9a.23

Reserved

0

26

9a.24

Reserved

0

27

9a.25

Reserved

0

28

9a.26

Reserved

0

29

9a.27

Reserved

0

30

9a.28

Reserved

0

31

9a.29

Reserved

0

32

Table B.14 Snapshot 16 Parameter Record Table Read (File F19)

Parameter No.

Parameter Name

Master Module Parameter Range

Element

Table B.15 Snapshot 8 Parameter Record Table Read (File F19)

Parameter No.

Parameter Name

Master Module Parameter Range

Element

9b.1

Timestamp; Year

1998 to 2097

1

Timestamp; Month, Date

257 to 3103
Month = Value/256
Date = Remainder of Value/256

2

Timestamp; Hour, Minute

0 to 5947
Hour = Value/256
Minute = Remainder of Value/256

3

Timestamp; Seconds, Hundreths

0 to 15203
Seconds = Value/256
hSeconds = Remainder of Value/256

4

9b.2

Reserved

0

5

9b.3

Avg L-L Voltage (in Delta modes) or Avg L-N
Voltage (in non-Delta modes)

0 to 9999x10

21

Volts

6

9b.4

Average Current

0 to 9999x10

21

Amps

7

9b.5

Total True PF

-100 to +100

8

9b.6

Total Real Power

0 to 9999x10

21

kW

9

9b.7

Frequency

0 to 75 Hz

10

9b.8

Voltage Unbalance

0 to 100%

11

9b.9

Current Unbalance

0 to 100%

12

9b.10

Total Reactive Power

0 to 9999x10

21

kVAR

13

9b.11

Number of Records Requested

1 to 489

14

9b.12

Number of Records Read so far

1 to 489

15

9b.13

Record Number Returned

1 to 489

16

9b.14

Internal Identifier

0 to 255

17