Ethernet Communication Card Data Tables B-3

1.15

Snapshot Interval -
Hours

0

19

0 to 32,767

1.16

Snapshot Interval -
Minutes

0

20

0 to 32,767

1.17

Snapshot Interval -
Seconds

0

21

0 to 32,767

1.18

Snapshot Buffer Type

0 = Fill and Stop
1 = Circular

1

22

0 to 1

1.19

Snapshot Param #1

(3)

See Table B.3

62

23

0 to 64

1.20

Snapshot Param #2

(3)

See Table B.3

63

24

0 to 64

1.21

Snapshot Param #3

(3)

See Table B.3

47

25

0 to 64

1.22

Oscillograph Type

(3)

0 = V2.10 or earlier
compatible mode
1 = 10.8 kHz, 1 capture
2 = 10.8 kHz, 2 captures
3 = 5.4 kHz, 1 capture
4 = 5.4 kHz, 2 captures
5 = 2.7 kHz, 1 capture
6 = 2.7 kHz, 2 captures

0

26

0 to 6

1.23

Oscillograph
Overwrite Timeout

(3)

1 to 4320 minutes

1

27

1 to 4320

1.24

Output Pulse Relay
No.

0 = None
1 = Relay 1
2 = Relay 2

0

28

0 to 2

1.25

Output Pulse
Parameter

0 = kWh Forward
1 = kWh Reverse
2 = kVarh Forward
3 = kVarh Reverse

0

29

0 to 3

1.26

Output Pulse
Increment

1 to 32766

1

30

1 to 32766

1.27

Output Pulse Width
(ms)

(4)

0, 40 to 2000

100

31

40 to 2000

1.28

Ch A 12 Cycle
Oscillogram

(5)

1 = Phase 1 Voltage
2 = Phase 1 Current
3 = Phase 2 Voltage
4 = Phase 2 Current
5 = Phase 3 Voltage
6 = Phase 3 Current
7 = Phase 4 Current

1

32

1 to 7

1.29

Ch B 12 Cycle
Oscillogram

(5)

1 = Phase 1 Voltage
2 = Phase 1 Current
3 = Phase 2 Voltage
4 = Phase 2 Current
5 = Phase 3 Voltage
6 = Phase 3 Current
7 = Phase 4 Current

2

33

1 to 7

Table B.2 Device Configuration Data Table - Write and Read (File N11)

Parameter No.

Parameter Name

Master Module Range

Default
Setting

Element

Range