Table 3.2 msg read data table locations – Rockwell Automation 1403-NENET Ethernet Communication Card Installation Instructions User Manual

Page 63

Advertising
background image

Publication 1403-IN005A-EN-P

Sample Ladder Listing C-3

N9

1

N9:0 Sequencer output

N10

Variable

N10:0 Sequencer Input

N11

3

N11:0 Sequencer input data
for configuration mode

N12

3

N12:0 Sequencer input data
for setpoint mode

N13

Variable

N12:0 Sequencer input data
for run mode

N20

2

N20:0 Number of setpoints

N20:1 Temporary storage for
setpoint address

N22

21

Setpoint #1 location

N23

N39

21

21

Setpoint #2 location

Setpoint #20 location

R6:0

Sequencer control

Table 3.2 MSG Read Data Table Locations

Data File Address
(Control/Data)

Data File Size

Description

N40/F70

30

Voltage/Current Data

N41/F71

34

Real-Time Power

N42/N72

46

Cumulative Power

N43/N73

45

Device Configuration

N44/N74

24

Communication
Configuration

N45/F75

34

Demand

N46/N76

33

Even Harmonic Distortion

N47/F77

33

Odd Harmonic Distortion

N48/F78

32

Even Harmonic Magnitude

N49/F79

31

Odd Harmonic Magnitude

N50/F80

31

Even Harmonic Phase

N51/F81

30

Odd Harmonic Phase

N52/N82

40

Diagnostic

N53/N83

39

Relay/setpoint

Table 3.1 Data Files

Data File Address

Data File Size

Description