Rockwell Automation 1403-NENET Ethernet Communication Card Installation Instructions User Manual

Page 18

Advertising
background image

Publication 1403-IN005A-EN-P

B-4 Ethernet Communication Card Data Tables

1.30

Oscillograph Buffer
Type

(5)

0 = Hold
1 = Overwrite

1

34

0 to 1

1.31

Number of Pretrigger
Cycles for the 12 Cycle
Oscillogram

(5)

-1 = No Pretrig
0 to +8 = Cycles

0

35

-1 to +8

1.32

IEEE 519 Max. Short
Circuit Current

(5)

0.0 to 10,000,000.0

0

36

0 to 9999

37

0 to 4

1.33

IEEE 519 Max.
Demand/Load
Current

(5)

0.0 to 10,000,000.0

0

38

0 to 9999

39

0 to 4

1.34

Save Status Changes
to Event Log

0 = No
1 = Yes

0

40

0 to 1

1.35

Vaux Voltage Mode

0 = AC
1 = DC

0

41

0 to 1

1.36

Filter Mode(1403-MM)
Enable THD (1403-LM)

1 to 3 (1403-MM)
0 to 1 (1403-LM)

2 (1403-MM)
0 (1403-LM)

42

1 to 3 (1403-MM)
0 to 1 (1403-LM)

1.37

Enable Min_Max Log

0 = No
1 = Yes

1

43

0 to 1

Reserved

44

(1) Available on 1403-MM firmware V2.0 or later and 1403-LM firmware V1.01 or later.

(2) This value is 1 for 1-Amp Master Module (Cat. No. 1403-MM01X) or 5 for a 5-Amp Master Module (Cat. No. 1403-MM05X).

(3) Available on firmware V3.00 or later (reserved in previous versions).

(4) For transitional KYZ pulse enter 0.

(5) 1403-MM only, not available on 1403-LM version.

Table B.2 Device Configuration Data Table - Write and Read (File N11)

Parameter No.

Parameter Name

Master Module Range

Default
Setting

Element