Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 10

Advertising
background image

1-6

Product Description

1503-UM053B-EN-P – June 2013

Table 1.A – Electrical Ratings

Main Input Voltage
(L1 to L2/N)

AC – 110 to 240 V rms, +10/-15%, 47 to 63 Hz
DC – 110 to 250 V, +10/-15%

Main Input Current
(L1 to L2/N)

Description

Contactor Ratings

(Amps)

Control Voltage

(AC or DC)

AC Rating

DC Rating

Inrush Current

400/800

120/240

25 A peak (1/2

cycle)

25 A peak

Idle Current
(Maximum without contactor coil

energized)

400/800

120/240

125 mA

35 mA

Hold Current ⊄ (maximum)

400/800

120/240

300 mA

100 mA

Close Current ⊄
(0.2 sec)

400

120

4.6 A

3.6 A

240

3.4 A

3.3 A

800

120

11.3 A

4.8 A

240

8.9 A

4.5 A

Trip Current (latch) ⊄
(0.2 sec)

400

120

7.0 A

3.7 A

240

3.6 A

2.0 A

800

120

7.0 A

3.3 A

240

4.3 A

1.9 A

Command Inputs
⊇ ⊂

AC – 70 to 240 V rms
DC – 70 to 250 V
Maximum on state current for open or close command:

11mA

AC

@ 276 V AC, 60Hz, T

A

= 60°C

2.4mA

DC

@ 276 V DC, T

A

= 60°C

Minimum on state current for open or close command:

2.5mA

AC

@ 70 V AC, 60Hz, T

A

= 60°C

1.2 mA @ 68 V DC, T

A

= 60°C

Maximum off state current for open or close command:

1.9 µA @ 60 V AC, 60 Hz, T

A

= 60°C

900 µA @ 60 V DC, T

A

= 60°C

Status Output Contacts

AC – 250 V rms, 5 A, R load; 2 A (reactive), PF = 0.4

DC – 30 V, 5 A, R load; 2 A (reactive), L/R = 7 ms

Standards and Approvals

CE, cULus, CSA, IEC pending

T

A =

Ambient Temperature

Includes idle current.

Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.

Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed. The Series C and D IntelliVACs are compatible with most PLC outputs,
and have been verified with Rockwell Automation OA type 120V triac outputs. See Chapter 3, Wiring Guidelines.