Chapter 5, Monitoring and troubleshooting, Chapter – Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 39

Advertising
background image

Chapter

5

1503-UM053B-EN-P – June 2013


Monitoring and Troubleshooting

Introduction

The IntelliVAC module has two light emitting diodes (LEDs) and relay
outputs to indicate the status of the contactor and the module. The LEDs

are visible on the front of the module and the relay outputs are accessed

on the bottom front of the module.

Figure 5.1 – IntelliVAC LEDs

Note:

This user manual contains information for both Series C and

Series D IntelliVAC versions. Refer to the correct information

below for the IntelliVAC series in use.

Module Status

The Module Status is indicated with a Green LED if the module is

functioning properly and has a valid configuration. If the module powers

up with an invalid configuration the LED will be Red (flashing once),

indicating a Fault condition which will not allow the contactor to close. If

the module powers up properly and experiences an undervoltage condition
when attempting to close the contactor or while the contactor is closed:

• Series C – the LED will be Red (Fault). If the contactor does not

close properly, a Fault is generated, the LED turns Red, and inputs

are inhibited until the module power is removed and reapplied.

• Series D/E – the LED will be yellow (flashing once). If the

undervoltage condition is corrected during the selected TDUV

interval (as set via DIP switch), then normal operation resumes.