Control with solid-state devices – Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 25

Advertising
background image

3-12

Installation and Wiring

1503-UM053B-EN-P – June 2013

Control with Solid-State Devices

When control devices that employ electronic or suppressed output
circuits are used in the rung(s) that control the inputs to the IntelliVAC,

alternate arrangements may be required. Devices employing transistor or

triac output circuits have finite impedance and allow a leakage current to

flow in the blocking or off state. Some PLC and I/O modules with relay
outputs have R-C snubber circuits across the contact to suppress voltage

transients generated during contact opening. The impedance of these

snubber circuits also allows leakage current to flow when the contacts are

open. The IntelliVAC input circuits have been designed such that typical
output leakage currents should not create unintended operation of the

contactor. The vast majority of control devices may be directly connected

to the IntelliVAC without any inappropriate operation occurring.


This situation can be prevented by consideration of the control devices

when designing the control system. With control devices that have

excessive leakage current (i.e. PLC or similar control devices) consider

using relay outputs with now suppression across the contacts. If this
cannot be done, consider the leakage current of the device to see if it is

compatible with the IntelliVAC inputs (see Table 1.A). If the control

device is not compatible consider using an interposing relay connected as

shown in Figure 3.6.

-

+

3

2

12

11

AUX

MOV

M

TCO

5

6

-

+

1

EC

CCO

4

9

10

M

CLOSE

N

G

OVERLOAD

*

CONTROL

POWER

FUSE

CONTROL POWER

M

M -IV

M -IV

L

CR

CR

SOLID STATE

OUTPUT

INPUT POWER

*

Refer to Table 3.A for recommended fuse sizing.

Figure 3.6 – Control with Solid-State Devices

Advertising