Installation and Wiring

1503-UM053B-EN-P – June 2013

Interface Connections

All other control interface connections are made at a twelve-pole
connector located on the top of the module. Refer to Figure 3.5 and

Table 3.B for connections (and Table 1.A for electrical ratings).

Refer to the

Wiring Guidelines section in this chapter for guidance in

making connections to the control circuit.

CONTACTOR INTERFACE

11 12

8

9

10

5

6

7

2

3

4

1

EX. CAP.

Figure 3.5 – Top side connections

Table 3.B – Terminal Assignments for IntelliVAC Interface Connections

Terminal No.

Terminal Designation

Description

1

External capacitor (negative) 

Power connection for TDUV or capacitor trip options

only

2

External capacitor (positive) 

3

Latch trip coil (common) 

Output for mechanical latch contactor trip coil

4

Latch trip coil 

5

Close coil (common)

Output to close coil of electrically held &

mechanical latch contactors

6

Close coil

7

Open / Jog command 

Input to open a mechanical latch contactor or jog

an electrically held contactor (mutually exclusive)

8

Open / Jog command (common) 

9

Close command 

Input to initiate the closure of electrically held and

mechanical latch contactors

10

Close command (common) 

11

Contactor auxiliary contact 

Input to indicate the state of the contactor

(typically wired to a normally closed auxiliary

contact)

12

Contactor auxiliary contact 

Refer to Table 1.A for electrical ratings.

No connection required if option is not used.

Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs. Consider means of

isolating/loading these signals, as required (using interposing relays or load resistors). Consult factory for assistance, if needed. The
Series C and D IntelliVACs are compatible with most PLC outputs, and have been verified with Rockwell Automation OA type 120V
triac outputs. See Wiring Guidelines.

For electrically held contactor, this command will energize the close coil output (CCO).

For mechanically held contactor, this command will energize the trip coil output (TCO).