Installation and Wiring

3-19

1503-UM053B-EN-P – June 2013


Motor Jogging Control

Note: Jog functionality can work with electrically held contactor only.

When used with electrically held contactors, the IntelliVAC allows close
commands every six seconds. This is to ensure the rated contactor duty

cycle of 600 operations per hour is not exceeded.

For motor jogging operations, the second control input, or OPEN
command, will close the contactor for as long as the input is present, and

open the contactor when the input is removed. (Refer to Figure 3.12.)

This method will bypass the standard six second motor re-start delay for

jogging purposes only. Operations will be limited to two starts every
twelve seconds.

A T T E N T I O N

A T T E N T I O N

If the TDUV feature is used, the contactor will
not open until the programmed TDUV time

has expired. Therefore, applications requiring
an immediate removal of power during

emergency stop conditions are not compatible

with the TDUV feature.

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

STOP

START

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

M-IV

15

16

CONTACTOR

STATUS

M

M-IV

M

+ -

JOG

M-IV

7

8

OPEN

* Refer to Table 3.A for recommended fuse sizing.

EMERGENCY STOP

(when required)

Figure 3.12 – Motor Jogging Control