Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 7

Advertising
background image

Product Description

1-3

1503-UM053B-EN-P – June 2013

IntelliVAC Features (cont.)

Anti-kiss and anti-pumping protection ensure that the vacuum

contactor close – open sequence occurs as expected, avoiding rapid

re-closure due to faulty control devices

Delayed restart protects the vacuum contactor by ensuring that the

rated duty cycle is not exceeded

Temporary jog function (electrically held contactors only) allows

the motor to be positioned for process set-up


IntelliVAC Versions

Series A

There are two versions of IntelliVAC control. The

first type is used to control vacuum contactors that are

electrically held, with a single electrical coil that is

economized electronically. The second is used to

control mechanically latched vacuum contactors.

Series B

There is a single version of IntelliVAC, to control

both electrically held and mechanically latched

vacuum contactors.

Series C

Updated version of the Series B module.

Series D

Minor functionality (firmware) enhancements

(primarily related to definition and handling of Faults

and Warnings).

Series E

Revised hardware to allow connection to the

IntelliVAC Plus or IntelliVAC MC> Removal of the

mini Din connector for flashing firmware (firmware is

now flashed using the IntelliVAC Plus or IntelliVAC

MC boards). New input circuits to reduce thermal
output, and decrease sensitivity to leakage current.

Refer to Chapter 6, for catalog numbers for each version of IntelliVAC.

Note:

A Series C, D or E IntelliVAC module can be used to replace

a Series A or Series B module. When replacing an older series

of IntelliVAC with a newer one, note that the Module and
Contactor Status outputs may function differently. Refer to

publication 1503-UM051C-EN-P and/or Chapter 5 of this

Advertising