Mechanical latch contactors – Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 30

Advertising
background image

Installation and Wiring

3-17

1503-UM053B-EN-P – June 2013

Capacitor Trip

The IntelliVAC can be configured to provide capacitor trip functionality
with mechanical latch contactors. A capacitor must be connected to the

IntelliVAC (terminals #1 and #2) in order to provide this capability. The

capacitor provides control power for the IntelliVAC as well as stored

energy to trip the contactor. Maximum recommended capacitor size is
1650 µF for 120V control or 330 µF for 240V control. Use of larger

capacitors will require a current limiting circuit to prevent opening the

control fuse on energization.


The IntelliVAC must receive an ‘OPEN’ command within a few seconds

of losing AC control power. This time limit depends on voltage and

capacitor size as shown in the table below. If the elapsed time exceeds this

limit, the contactor cannot be tripped by IntelliVAC. In this case, the
contactor can be tripped by pressing the release button on the door in

front of the contactor.

A separate voltage source is needed to provide the ‘OPEN’ command. This
may be taken from the external capacitor as shown in Figure 3.11.

Table 3.C – Mechanical Latch Contactor – Capacitor Trip Times

Contactor

Rating

Nominal Voltage

(Vac)

Actual

V

input

(Vac)

Ext. Capacitor

(µF)

Max. time

for trip

(sec)

400 Amp

120

120

1650

3.5

110

2.7

100

1.7

240

240

330

7.5

200

4.7

Note: Minimum capacitor voltage ratings:

• 120V applications – 200V DC (250V DC preferred)

• 240V applications – 400V DC (450V DC preferred)

Mechanical Latch Contactors

Advertising