Wiring guidelines mechanical latch contactors – Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 29

Advertising
background image

3-16

Installation and Wiring

1503-UM053B-EN-P – June 2013


IntelliVAC control may be used for mechanical latch contactors.

A momentary control signal is needed to close the contactor, and a second
momentary control signal is needed to open the contactor. The

momentary open/close commands must be at least 50 milliseconds in

duration.

Refer to Figure 3.10 for a typical mechanical latch control scheme.

Note:
1. A mechanical latch contactor may already be closed when power is

applied to the IntelliVAC control module.

2. It is permissible to apply an open command to the IntelliVAC

module as power is re-applied.

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

CLOSE

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

CC

M-IV

M

MOV

TC

M

+ -

M-IV

7

8

OPEN

OPEN

OVERLOAD

* Refer to Table 3.A for recommended fuse sizing.


Figure 3.10 – Mechanical Latch Contactor Control

Wiring Guidelines Mechanical

Latch Contactors

Advertising