Chapter 2

Run Up/Coast Down Extension Module

Use these descriptions to help you configure the parameters in the Run Up/Coast
Down Setup screen.

Table 2 - Run Up/Coast Down Setup Parameters

Parameter

Description

Values/Comments

Transducer

Specifies the type of sensor used on Connector A, this is typically
Accel (g).

The specified sensor type determines available options and
engineering units for subsequent setup fields.

Accel ICP (g) (default)

Accel (g)

Accel ICP (m/s

2

)

Accel (m/s

2

)

Vel ICP (mm/s)

Vel (mm/s)

Vel ICP (ips)

Vel (ips)

Disp (mils)

Disp (µm)

Volts AC

User (EU)

Sens (mV/EU)

The transducer sensitivity in millivolts (MV) per engineering units
(EU).

1…2000 (mV/EU)

100 (default)

Range (EU)

The expected maximum amplitude range value for the incoming input
signal.

The range should accommodate for unexpected events. If you are
unsure about the range value, set the range 10 to 20 times higher
than expected.

.1 EU

.2 EU

.5 EU

1 EU

2 EU (default)

5 EU

10 EU

20 EU (default)

50 EU

100 EU

200 EU

500 EU

1000 EU

2000 EU

Max M/c Speed

The maximum speed that the shaft will reach in rpm.

This is used with Max No Orders to determine the sampling rate.

10…60000 rpm

3600 rpm (default)

Max No Orders

The maximum number of shaft orders of interest during analysis.

This is used with Max M/c Speed to determine the sampling rate.

1 to 166

32 (default)

Mode

The method for initiating the data collection.

Runup - The data collection starts when the machine speed

rises above Start Spd.

Coast down -The data collection starts when the machine

speed falls below Stop Spd.

Manual - Manually start data collection by pressing F4 (Start).

No tachometer signal is required for this mode.

Runup (default)

Manual

Coastdown