Chapter 1

Installing Optional Extension Modules

4.

Apply power to the data collector.

5.

From the Main Menu, select Setup Utility and press Enter.

6.

Press 0 (Shift) to display the second set of functions.

The Extension Manager function remains on the screen for about
3 seconds after releasing 0 (Shift).

7.

Press F1 (Extn Mgr).

The Extension Manager screen appears showing the current extension
module installations.

8.

Press 0 (Shift) to display the Install extension function.

9.

Press F2 (Install) to install the new extension module.

Extension Manager