Chapter 2

Run Up/Coast Down Extension Module

3.

Attach a transducer to the bearing house.

4.

Start the machine or stop the machine as needed.

5.

From the RUDC Setup screen press F3 (Start).

The RUCD - Taking Data screen appears.

The Dynamix 2500 data collector begins collecting run up or coast down
data based on the parameters you selected. The state of the machine is
indicated on the screen.

Data collection is complete when the specified Stp Speed or Maximum
Acquisition Time is reached, or you press F3 (Stop).

State

Description

Armed

The machine speed has not reached the Start Spd and data collection has
not yet started.

At any time during this state, you can press F3 (Start) to manually start
data collection.

Acquiring

The machine speed has reached the Start Spd and data collection has
started.

At any time during this state, you can press F3 (Stop) to manually stop
data collection.

Error-Clipped

An error occurred during data collection. If a sensor’s Range setting is too
small to accommodate the signal’s amplitude, a message displays in the
message error.

Press F4 (Back) to return to the RUCD - Setup screen and increase the
Range setting.

Current Speed of Machine

Current Overall
Vibration Reading

Maximum Acquisition Time in the
Armed State
Remaining Recording Time in the
Acquiring State

Message Area