2–4

Configuring the Module

Configuring the module

As you configure your module, you should complete the I/O image
table. First, size the I/O using switch SW3. Next, set the rack address
using switch SW1. Finally, select the starting group, last rack setting,
fault action, and baud rate using switch SW2. For more information
on the I/O image table, refer to the example below and Chapter 4.

I/O Image Table

Example I/O Image Table

In this example, we use the factory-default settings. We use rack 2,
and record it as our address. Because we are using a full rack, we use
starting group 0, so block transfer starts at word 0.

Remote
I/O
Address

Reserved For:

Minimum
Required
Rack Size

Starting
Group

Output Image

Input Image

1/4 Rack

0, 2, 4, or 6

1/2 Rack

0, 2, or 4

3/4 Rack

0 or 2

Full Rack

0 only

Remote
I/O
Address

Reserved For:

Minimum
Required
Rack Size

Starting
Group

Output Image

Input Image

020

Block Transfer

Block Transfer

1/4 Rack

0, 2, 4, or 6

021

Logic Command

Logic Status

022

Reference

Feedback

1/2 Rack

0, 2, or 4

023

Datalink A

Datalink A

024

Datalink A

Datalink A

3/4 Rack

0 or 2

025

Datalink B

Datalink B

026

Datalink B

Datalink B

Full Rack

0 only

027

Switch

Settings
8 ---> 1

Description

00011111

Block transfer is enabled.

Logic command/status is enabled.

Reference/feedback is enabled.

Datalink A is enabled.

Datalink B is enabled.

Truncate last datalink is disabled.

00011011

Starting group is 0.

This is not the last rack.

Drive will fault when communications
are disrupted, and it will hold last state
when the controller is placed in
program/reset/test.

Remote I/O baud rate is 57.6K.

10111100

Rack address is 2.

Off = 0
On = 1

Off = 0
On = 1

Off = 0
On = 1