2–12

Configuring the Module

4. Slide the switches to their appropriate positions.

Settings take effect when a module or board first receives power.
When you change a setting, you must remove and then reapply power
for the new setting to take effect.

Setting the Remote I/O Baud Rate

SW 2.8 and SW 2.7 set the baud rate at which the Remote I/O module
communicates.

Figure 2.11

Remote I/O Baud Rate Switches

To change the baud rate, you need to:

1. Refer to the following table to determine settings for SW2.8 and

SW2.7:

2. Slide the switches to their appropriate positions.

Settings take effect when a module or board first receives power.
When you change a setting, you must remove and then reapply power
for the new setting to take effect.

!

ATTENTION: Injury or equipment damage can result
from loss of PLC or Controller Logic Commands (Stop,
Start, etc.) when all these conditions are true:

module firmware 3.04 or lower.

230.4k baud rate.

block transfer is enabled (DIP switch SW3.1 ON).

block transfers to the module are used (in the ladder

program or by DriveTools/DriveTools32 using a

Remote I/O pass thru connection).

Do not use the 230.4k baud rate if your module firmware
is 3.04 or earlier and if your program uses block transfers.
Use the 57.6k or 115.2k baud rate instead.

Baud Rate

Switch 2.8

SW2.7

57.6 K

0

0

115.2 K

0

1

230.4 K

1

0

Off = 0
On = 1

Use SW 2.8 and SW 2.7 for setting
the baud rate.