Scanport product settings – Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual

Page 44

Advertising
background image

4–6

Creating Ladder Logic Programs

SCANport Product Settings

Logic Command bits

In our example, we are using a 1336 PLUS drive. The Logic
Command bits for it are:

The 1305 drives, 1336 PLUS II drives, and 1336 Spider drives use the
same Logic Command and Logic Status data. For other drives, refer
to their user manuals.

Logic Command Bits

Function

Description

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Stop

1=Stop, 0=No Operation

X

Start

1=Start, 0=No Operation

X

Jog

1=Jog, 0=No Operation

X

Clear Faults

1=Clear, 0=No Operation

X

X

Direction

00=No Operation, 01=Forward,
10=Reverse

X

Local

1=Local, 0=Multiplexed

X

MOP Increment

1=Increment MOP, 0=No Operation

X

X

Accel Rate Select

00=No Operation, 01=Rate 1, 10=Rate 2

X

X

Decel Rate Select

00=No Operation, 01=Rate 1, 10=Rate 2

X

X

X

Reference
Selection

000=No Operation

001=External Reference 1 (Par 5)

010=External Reference 2 (Par 6)

011=Preset 3

100=Preset 4

101=Preset 5

110=Preset 6

111=Preset 7

X

MOP Decrement

1=Decrement MOP, 0=No Operation

Asserting a 1 will stop the product.