Installing the Module

Remote I/O Cables

Remote I/O communications modules are connected to Remote I/O
links with twinaxial cable used for Remote I/O and Data Highway
Plus (DH+) communications. When selecting a cable, remember the
following:

Only 1770-CD Belden #9463 is tested and approved for RIO and
DH+ installations. Using other cables is at your own risk.

The total cable length depends on the baud rate that you are
using. Refer to the following table:

All three of the following conductors must be connected at each
node.

Do not use a star topology. Only two cables may be connected at
any wiring point. You can use a series topology and daisy-chain
two wires at a point.

Selecting a Termination
Resistor

You must terminate both ends of a Remote I/O link to ensure proper
operation. This termination is required only at the ends of the
physical cable. Each Remote I/O link should have exactly two
termination resistors.

If the device that you connect is an end device on the Remote I/O
link, it must be terminated. Refer to the following table to select a
resistor.

Important: You must use an 82 ohm external termination resistor if

the link is operating at 230.4 kbps.

Baud Rate

Maximum Length

57.6 K

3,048 m (10,000 ft)

115.2 K

1524 m (5,000 ft)

230.4 K

762 m (2,500 ft)

Color

Description

Blue

1

Shield

SH

Clear

2

Device

Description

Programmable Controller Refer to its manual.
1336-GM1

(Using Jumpers)

Set J2 in position 1-2 for termination and 2-3 for no termination.
Refer to Figure 3.8. The jumper enables a 150 ohm resistor

.

1203-GD1, 1203-GK1, or
1336-GM1

(Using an external termi-
nation resistor)

Connect a resistor between terminals 1 and 2 on the Remote I/O
connector. Refer to Figure 3.4.

Use an 82 ohm termination resistor unless a device requires a
150 ohm termination resistor

.

The following scanners require 150 ohm termination resistors on the RIO link: 1771-SN, 1772-SD,

1772-SD2, 1775-SR, 1775-S4A, 1775-S4B, 6008-SQH1, and 6008-SQH.
The following adapters require a 150 ohm termination resistors on the RIO link: 1771-AS, 1772-ASB
(Series A), 1771-DCM.
The following devices require a 150 ohm termination resistors on the RIO link: 1771-AF.