B-20, Fault queue size read, Plc block transfer instruction data – Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual

Page 84: Message operation, Example

Advertising
background image

B–20

Supported Block Transfer Messages

Fault Queue Size Read

Fault Queue Size Read gets the number of fault entries allowed in
the fault queue.

PLC Block Transfer Instruction Data

PLC request instruction length: 3 words
Drive response instruction length: 4 words

Figure B.13

Message Structure

Message Operation

Fault Queue Size Read reads back the size of the fault queue
available in the product. Each product may have a different number of
fault queue entries available for storage.

If an error has occurred, word 1 of the response returns a value of
-30975.

Example

In this example, a 1336 PLUS drive was used. This product has a fault
queue of four storage locations available to store faults. This value is
seen in word 3 of the response header message.

Data File Format

* Example only — These values vary depending on parameters and products.

Header

Word 0

PLC Decimal Value

1793

Header

Word 1

Header

Word 2

PLC Request

Header Word 0

Header Word 1

Header Word 2

Message Length

Message Length

PLC Decimal Value

1793 — Message OK

–30975 — Message Error

0

Drive Response

3

0

4

Data

Word 3

Fault Queue Size

or Error Code

0

1

2

3

4

5

6

7

8

9

PLC request

3

1793

0

Drive response

4

1793

0

4*