Configuring the Module

2. Refer to the following table to set SW 2.2 and SW 2.1:

3. Slide the switches to their appropriate positions.

Settings take effect when a module or board first receives power.
When you change a setting, you must remove and then reapply power
for the new setting to take effect.

Setting the Last Rack Switch

SW 2.3 lets you notify a controller that the connected product is the
last device with this rack address. You must set this switch if a
product is the last device with this rack address and you are using a
PLC-2 controller. It is recommended that you set this switch when
you are using other controllers.

Figure 2.9

Last Rack Switch

To edit the last rack settings, you need to:

1. Refer to the following table to determine the switch setting for

SW 2.3:

2. Slide the switch to its appropriate position.

Settings take effect when a module or board first receives power.
When you change a setting, you must remove and then reapply power
for the new setting to take effect.

Starting Group

SW 2.2

SW 2.1

0

1

1

2

0

1

4

1

0

6

0

0

Setting

SW2.3

Not Last Rack

0

Last Rack

1

Off = 0
On = 1

Use SW2.3 for setting the
last rack.