Connecting the option to the 1329i unit, Connecting the option to the 1329i unit -2 – Rockwell Automation 1329I DeviceNet Option FRN 1.XXX User Manual

Page 14

Advertising
background image

2-2

Installing the DeviceNet Option

Connecting the Option to
the 1329I Unit

1. Verify that power has been removed from the 1329I unit and network.

2. Use static control precautions.

3. Remove the cover on the 1329I unit by loosening the four cover screws.

The display cable is designed to disconnect when the cover is removed.

Figure 2.1 Removing the Cover

4. Mount the DeviceNet option. Tighten all screws to 2.6 N-m (23 in.-lb.).

Use the washer in the location shown in

Figure 2.2

to ground the option.

5. Connect the unit cable on the DeviceNet option to connector P3 on the

1329I unit. Connector P3 is next to the control signal terminal block.

Figure 2.2 Mounting the DeviceNet option

6. Before reconnecting the cover (

Figure 2. 5on page 2-5

), commission the

1329I unit and connect it to the network (instructions in this chapter).

!

ATTENTION: Risk of injury or death exists. A 1329I
Integrated Drive/Motor and DeviceNet network may contain
voltages that can cause injury or death. Remove power from the
1329I unit and network, and then verify that bus voltage has
discharged to a zero before working on them.

!

ATTENTION: Risk of equipment damage exists. The option
contains ESD (Electrostatic Discharge) sensitive parts that can
be damaged if you do not follow ESD control procedures. Static
control precautions are required when handling the drive. If you
are unfamiliar with static control procedures, refer to Guarding
Against Electrostatic Damage
, Publication 8000-4.5.2.

2.6 N-m

(23 in-lb)

Unit Cable