Configuring the 1329I Unit and DeviceNet Option

3-9

Setting the Communications
Fault Action

The communications fault action determines how the 1329I unit and
DeviceNet option respond when communications are disrupted (e.g.,
disconnected cable). By default, the 1329I unit is faulted and stopped. You
can change this setting if your application requires a different setting.

1. In the Device Configuration - Enhanced Mode dialog box (

Figure 3.8

),

double-click Parameter 109 - [DNet Fault Mode]. The Device
Configuration - Modify Boolean Parameter dialog box appears.

Figure 3.14 Modifying the Fault Action Parameter

2. Select the appropriate setting for your application, and then click Save to

Device.

3. Click OK to close the dialog box.

!

ATTENTION: Hazard of injury or equipment damage exists.
Parameter 109 - [DNet Fault Mode] determines the action of
the option and connected 1329I unit if communications are
disrupted. By default, this parameter faults and stops the 1329I
unit. You can set this parameter so that the 1329I unit continues
to run. Precautions should be taken to ensure that the setting of
this parameter does not create a hazard of injury or equipment
damage.

Setting

Description

Fault and Stop

The 1329I unit is faulted and stopped.

Ignore

The disruption is ignored and the 1329I unit
continues to run.