Troubleshooting

Solving Potential Problems

9

0x6312

F.Id

EEPROM Drive
ID

Contents of the EEPROM is
corrupted.

Reset parameters to default values
and cycle power.

If fault persists, replace 1329I unit.

10

0x7700

F.dcn

Keypad
Disconnect

Keypad cable disconnected
while 1329I unit under power.

Remove power from the 1329I unit.
Check keypad cable connection.
Reapply power to the 1329I unit.

11

0x7701

F.ddP

Keypad Fixed
Pattern

Keypad cable connected while
1329I unit under power.

Remove power from the 1329I unit.
Check the keypad cable connection.
Reapply power to the 1329I unit.

12

0x7702

F.dSF

Keypad
Redundant Start

Keypad hardware failure.

Remove power from the 1329I unit.
Check the keypad cable connection.
Reapply power to the 1329I unit.

13

0x5301

F.rSF

TB Redundant
Start

Regulator board failure.

Remove power from the 1329I unit.
Check the keypad cable connection.
Reapply power to the 1329I unit.

14

0x7703

F.drc

Keypad Connect

Keypad cable connected while
1329I unit under power.

Remove power from the 1329I unit.
Check the keypad cable connection.
Reapply power to the 1329I unit.

15

0x3221

F.LU

Under Voltage
while Running

Low input line or temporary loss
of input line.

Check input line to verify voltage is
within operating specifications.

20

0x6311

F.dnE

DNet EEPROM
Fault

DeviceNet option EEPROM has
invalid data.

Use Parameter 113 - [Reset] to reset
option parameters to factory defaults.

21

0x7502

F.dnU

DNet
Unrecoverable
Fault

No communication is occurring.
Fault occurs when duplicate
node address exists or wrong
data rate is set.

Check DIP switch settings on the
DeviceNet option for proper data rate
and node address. If DIP switches 7
and 8 on the DeviceNet option are
both set to On, check Parameter 103 -
[NV MAC ID] and Parameter 104 - [NV
Baud Rate]. Then reset the option.

22

0x7500

F.dnP

No DNet Power

24 volt network power is not
detected.

Check DeviceNet connector at
Communication Module. Also, check
network’s power supply.

23

0x7501

F.dnL

DNet Lost I/O
Connection

Polled I/O connection timed out.

Check DeviceNet master device for
correct operation (i.e., powered up,
scanner online, etc.).

24

0x7504

F.dnF

DNet Forced
Fault

Control Supervisor Object
(Class Code 0x29) attribute 17
was set to 1.

Clear fault.

25

0x7505

F.dnC

DNet Comm Fault Communication failure between

DeviceNet option and unit.

Check the unit cable connecting the
DeviceNet option and 1329I unit.

Fault Codes

(1)

Name

Description

Corrective Action

Parameter
Value

DeviceNet Display

(1)

Parameter fault codes are viewed in Parameter 10 - [Last Fault]. DeviceNet fault codes are read from Class 0x29, Instance 1, Attribute 13. Display
fault codes are viewed on the LED display on the local operator control keypad.

Description

Solution

Parameters settings are not
taking effect, or switch settings
are not taking effect.

Check the setting of DIP switch 10 on the 1329I unit (

Figure 2.3

).

If this switch is On, then the 1329I unit uses the settings of the
drive parameters in EEPROM. If it is Off, then the 1329I unit uses
the settings of the DIP switches and rotary switches on the board.
1. Set the switch as desired.
2. Cycle power to the 1329I unit.

Unit uses an incorrect data rate
or node address.

Check the setting of DIP switch 7 and 8 on the DeviceNet option
(

Figure 2.3

). If both switches are On, the 1329I unit uses the node

address set in Parameter 103 - [NV MAC ID] and the data rate set
in Parameter 104 - [NV Baud Rate]. Otherwise, the 1329I unit
uses the values set using the DIP switches as specified in the

Commissioning the 1329I Unit for DeviceNet

section in

Chapter 2

.