Parameter list – Rockwell Automation 1329I DeviceNet Option FRN 1.XXX User Manual

Page 57

Advertising
background image

Parameters

B-3

Parameter List

#

Object
Mapping

Name and Description

Access
Rule

(1)

Units/
Range

Factory
Default

Drive Display Parameters
01

0x0F-1-1

Command Frequency
Value of the presently selected speed reference.

Get

0.1 Hz

None

02

0x0F-2-1

Output Frequency
Output frequency to the motor.

Get

0.1 Hz

None

03

0x0F-3-1

Output Voltage
Output voltage to the motor.

Get

1 Volt

None

04

0x0F-4-1

Output Current
Output current to the motor.

Get

0.1% of
Rated
Current

None

05

0x0F-5-1

Load Current
Output current to the motor due to the load.

Get

0.1% of
Rated
Current

None

06

0x0F-6-1

Bus Voltage
DC Bus voltage level.

Get

1 Volt

None

07

0x0F-7-1

Power Unit Temperature
Temperature of the 1329I unit.

Get

1 °C

None

08

0x0F-8-1

Analog Input
The value of the analog speed reference input (terminal 2 or 3 on the control signal terminal
block).

Get

0.1% of
Full Scale

None

09

0x0F-9-1

TB Input Status

The on (1) and off (0) state of the inputs to the control signal terminal block:

Get

Bits

None

10

0x0F-10-1

Last Fault
Fault number for the most recent fault.
0 = No Fault

11 = Keypad Fixed Pattern

1 = Function Loss

12 = Keypad Redundant Start

2 = Over Current

13 = TB Redundant Start

3 = Motor Overload

14 = Keypad Connect

4 = Over Voltage

15 = Under Voltage Running

5 = Under Voltage Stop

20 = DNet EEPROM Fault

6 = Over Temperature

21 = DNet Unrecoverable Fault

7 = Communication Loss

22 = No DNet Power

8 = Parameter Checksum

23 = DNet Lost I/O Connection

9 = EEPROM Drive ID

24 = DNet Forced Fault

10 = Keypad Disconnect

25 = DNet Comm Fault

Refer to

Chapter 7

for troubleshooting procedures.

Get

0 to 24

None

Drive Program Parameters
30

0x0F-30-1

Minimum Frequency
Lowest frequency that the drive will output continuously. Its value must be less that Parameter
31 - [Maximum Frequency].

Get/
Set

(2)

0 Hz to
60 Hz

0 Hz

31

0x0F-31-1

Maximum Frequency
Highest frequency that the drive will output. Its value must be greater that the value of
Parameter 30 - [Minimum Frequency].

Get/
Set

(2)

50 Hz to
120 Hz

60 Hz

(1)

Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the 1329I Integrated drive/motor is set to On (

Figure 2.3

).

(2)

The parameter can be set only when the drive is stopped.

(3)

The parameter can be set only when the 1329 Integrated drive/motor does not have an active I/O connection.

Bit 7 Bit 6 Bit 5

Bit 4 Bit 3 Bit 2

Bit 1 Bit 0

Bit 8

Bit 9

Bit 10

Bit 11

Bit 12

Bit 13

Bit 14

Bit 15

Stop

Start

Reset

Forward/Reverse

Function Loss

RPM/Percent Load Display

Not Used

Not Used

Speed Preset 0

Speed Preset 1

Speed Preset 2

Not Used