Understanding the COMM
Status Indicator

The COMM status indicator provides status information on the DeviceNet
option.

Important: When power is first applied to the DeviceNet option, the

COMM status indicator flashes green for 1/4 second, red for
1/4 second, and then goes blank while the communication
module finishes its initialization.

Color State

What It Means:

What To Do:

None

The option is not receiving power from
the network.

Check DeviceNet power and cable
connections and the power
connection on the DeviceNet
terminal block.

Red

Solid

Diagnostics test failed on power-up/
reset. Internal fault exists.

Cycle power to the 1329I unit and
network.

If the fault still exists, return the
option.

Duplicate DeviceNet node address.
Two nodes cannot have the same
address.

Reset DIP switches 1 through 6 on
the DeviceNet option using a
unique address and then cycle
power.

If DIP switches 7 and 8 on the
DeviceNet option are both set to
ON, change the value of P103 -
[NV MAC ID]
to a unique address
and then cycle power.

Invalid data rate.

Reset DIP switches 7 and 8 on the
DeviceNet option to a valid data
rate and the cycle power.

If DIP switches 7 and 8 on the
DeviceNet option are both set to
ON, change the value of P104 -
[NV Baud Rate]
to a valid data rate
and then cycle power.

Red

Flashing I/O connection timed out.

Reset the DeviceNet master device.

Green Solid

Normal operating state and device is
allocated to a master.

No action required.

Green Flashing Device is online but not allocated to a

master.

Verify that the DeviceNet master has
the correct configuration information for
the DeviceNet option (node address,
input assembly, and output assembly).