Set jumper jw4 -5, Set jumper jw4 – Rockwell Automation 1746-BAS-T SLC 500 Basic Basic-T Modules User Manual

Page 39

Advertising
background image

Publication 1746-UM004B-EN-P - December 2005

Install and Wire Your Module 3-5

Use the worksheet in Appendix B to document the selected jumper
setting of jumper JW3.

Set Jumper JW4

Use jumper JW4 to select one of the following configurations for the
module ports.

• PRT1 Port – Program port with default communication settings

PRT2 Port – ASCII interface port
DH485 Port – Runtime DH485 operation only

• PRT1 Port – ASCII interface port

PRT2 Port – ASCII interface port
DH485 Port – Program port with DH485 protocol

• PRT1 Port – Program port with programmed communication

settings
PRT2 Port – ASCII interface port
DH485 Port – Runtime DH485 operation only

• PRT1 Port – Program port with programmed communication

settings
PRT2 Port – DF1 protocol
DH485 Port – Disabled

Figure 3.5 JW4 Pin Assignments and Settings

3 5

1

4 6

2

PRT1 Port = Program port with
default communication settings
PRT2 Port = ASCII interface port
DH485 Port = Runtime DH485 only

Pin Assignments

PRT1 Port = ASCII interface port
PRT2 Port = ASCII interface port
DH485 Port = Program port with DH485 protocol
(shipped configuration)

PRT1 Port = Program port with programmed communication settings
PRT2 Port = ASCII interface port
DH485 Port = Runtime DH485 only

PRT1 Port = Program port with programmed communication settings
PRT2 Port = DF1 protocol
DH485 Port = Disabled