Publication 1746-UM004B-EN-P - December 2005

3-6 Install and Wire Your Module

Use the worksheet in Appendix B to document the selected jumper
setting of jumper JW4.

Documenting your selection provides others with information
necessary to integrate the module with their SLC 500 fixed or modular
controllers.

Install Your module

Once you have unpacked and set the jumpers on your module, you
are ready to install it in your:

• SLC 500 fixed controller expansion chassis.
• SLC 500 modular controller 1746 I/O chassis.

Your BASIC module or BASIC-T module may be installed in any open
slot of an SLC 500 1746 I/O chassis except the first slot of the first
chassis. The first slot is reserved for the processor or adapter module.

IMPORTANT

The first setting shown in Figure 3.5 is the default
configuration. When the jumper is set in this
position, the module always powers up in Command
mode at 1200 KB, no parity, 8 data bits, and 1 stop
bit.

ATTENTION

All other jumper settings for JW4 are illegal and may
cause damage to the module.

IMPORTANT

When DF1 protocol is selected for port PRT2, port
DH485 is not available for DH485 programming or
runtime operation.

DF1 communication must be enabled through the
BASIC program.