Programming Overview 4-15

Figure 4.3 Data Flow Between the SLC Processor and Port PRT2 of the Module

In addition, the commands in the following table provide status of and
control over the data transfer between the SLC processor and port
PRT2 of the module.

CALL 118

Allows unsolicited writes from a remote SLC or PLC node.

CALL 122

Reads a PLC data file and transfers it to the SLC I/O or M files.

CALL 123

Transfers data from the SLC I/O or M files to a remote PLC.

Command

Purpose

SLC Processor

CALL 123

CALL 23

CALL 22

CALL 122

CALL 118

PRINT#

INPUT#

INPL#

INPS#

GET#

PRT2 OUTPUT QUEUE

PRT2 INPUT QUEUE

256 bytes

256 bytes

Port PRT2

1746-BAS or 1746-BAS-T Module

Command

Purpose

MODE

Sets the port parameters of PRT1, PRT2, and DH485.

CALL 16

Enables interrupt capability when a DF1 packet is received.

CALL 17

Disables the DF1 packet interrupt capability.

CALL 30

Sets the port parameters for PRT2.

CALL 31

Displays the current PRT2 port configuration on the program port terminal
screen.

CALL 35

Retrieves the current character in the 256 character input buffer of port PRT2.

CALL 36

Retrieves the number of characters in the input or output buffer of port PRT2.

CALL 37

Clears the peripheral port input and/or output buffers.

CALL 97

Enables the DTR signal for port PRT2.

CALL 98

Disables the DTR signal for port PRT2.

CALL 108

Enables DF1 driver communications. You must use this CALL in conjunction
with CALLs 16, 17, 118, 122, and 123.

CALL 110

Prints the complete output buffer with addresses, front pointer, and number of
characters in the buffer to the console device.

CALL 111

Prints the complete input buffer with addresses, front pointer, and number of
characters in the buffer to the console device.

CALL 113

Disables DF1 driver communications.