Specifications, Module hardware specifications, Appendix a – Rockwell Automation 1746-BAS-T SLC 500 Basic Basic-T Modules User Manual

Page 71: Module hardware specifications -1, Appendix

Advertising
background image

1

Publication 1746-UM004B-EN-P - December 2005

Appendix

A

Specifications

Module Hardware
Specifications

The module hardware specifications are listed in the following tables.

Specification

Value

Power Supply Loading at
5V dc

0.150 A (module only)

0.150 A (module with link coupler)

Power Supply Loading at
24V dc

0.070 A (module only)

0.125 A (module with link coupler)

(2)

(2)

If a Hand-held Terminal, Data Table Access Module, or interface converter is connected to the link coupler,
the additional backplane power draw of these components must be added to the 0.125 listed in the table
above. This only applies when the module is connected to the network via the link coupler and 1747-C10
cable or 1747-C11 cable. This does not apply when the 1747-C13 cable is used.

Noise Immunity

NEMA Standard ICS 2-230

Vibration

Displacement: 0.015 in., peak-to-peak at 5...57 Hz

Acceleration: 2.5 g at 57...2000 Hz

Shock (operating)

30 g

Port Isolation

(1)

Port PRT1
Port PRT2
Port PRT1 to Port PRT2

(1)

Port DH485 is not isolated.

710V dc for 1 minute (backplane to port)
710V dc for 1 minute (backplane to port)
710V dc for 1 minute (port PRT1 to port PRT2)

Ambient Temperature
Rating

Operating: 0...+60 °C (+32...+140 °F)
Storage: -40...+85 °C (-40...+185 °F)

Humidity

5...95% without condensation

Clock/Calendar Accuracy

±1 minute/month at 25 °C (77 °F)
+0, -6 minute/month at 60 °C (140 °F)

Certification

Value

Agency Certification

c-UL-us listed
Class I, Groups A, B, C or D, Division 2
CE compliant for all applicable directives
C-Tick marked for all applicable acts