Rockwell Automation 1746-BAS-T SLC 500 Basic Basic-T Modules User Manual

Page 68

Advertising
background image

Publication 1746-UM004B-EN-P - December 2005

4-20 Programming Overview

Figure 4.6 Data Flow Between the Module and SLC Processor

In addition, the commands in the following table provide status of and
control over the data transfer between the SLC processor and module.

For more information regarding the use of these commands, refer to
the BASIC Language Reference Manual, publication 1747-RM001.

The following table lists module buffer addresses. Refer to page 4-1
for more information regarding module buffer addresses.

SLC Processor

CALL 53

16 bytes

SLC OUTPUT

IMAGE

BASIC INPUT

BUFFER

BASIC

OUTPUT

BUFFER

CALL 14/15

CALL 24/25

CALL 56

CALL 54

CALL 57

16 bytes

128 bytes

128 bytes

SLC INPUT IMAGE

SLC M0

SLC M1

1746-BAS or 1746-BAS-T Module

Command Purpose

CALL 51

Checks if the CPU output image buffer was updated.

CALL 55

Checks if the CPU input image buffer was read by the processor.

CALL 58

Checks if the CPU M0 file was updated.

CALL 59

Checks if the CPU M1 file was read by the processor.

CALL 86

Checks if the DH485 interface file was updated.

CALL 87

Checks if the DH485 interface file was read by an external device.

CALL 120

Clears the module input and output buffers.

Address

BASIC Input/Output Buffer Address

M1:e.s

100...163

M0:e.s

100...163

I:e.s

200...207

O:e.s

200...207

CIF in

0...39

CIF out

0...39