Slc fault codes, Slc fault codes -21 – Rockwell Automation 1746-BAS-T SLC 500 Basic Basic-T Modules User Manual

Page 69

Advertising
background image

Publication 1746-UM004B-EN-P - December 2005

Programming Overview 4-21

The SLC processor and module operate independently of each other.
The following CALLs allow the SLC processor and module to interrupt
each other.

SLC Fault Codes

Fault codes are reported in word 6 of the SLC processor status file.
The format of the status word and applicable error codes are shown
below:

Figure 4.7 SLC Fault Code Placement

CALL

Purpose

CALL 16

Enables interrupt capability when a DF1 packet is received.

CALL 17

Disables the DF1 packet interrupt capability.

CALL 20

Enables SLC processor interrupt capability.

CALL 21

Disables SLC processor interrupt capability.

CALL 26

Generates an interrupt to the SLC processor.

4-digit Hex Number

Slot Number

Fault Code

SLC
Fault
Code

Description

Possible Cause

Recommended Action

57H

Module has not
responded to a lock
shared memory command
within the required time
limit.

Module hardware problem.

Cycle power to the
module to re-initialize
parameters and re-run
the program.

Module internal stacks,
pointers (if XBY instructions
are used) are corrupted by the
user program.

58H

Module generated a
generic fault.

Module hardware problem.

Verify that module is
configured correctly
(correct I/O and M files).
Cycle power to the
module to re-initialize
parameters and re-run
the program.

Module internal stacks,
pointers (if XBY instructions
are used) are corrupted by the
user program.

59H

Module did not complete
a command within the
required time limit.

Module hardware problem.

Cycle power to the
module to re-initialize
parameters and re-run
the program.

Module internal stacks,
pointers (if XBY instructions
are used) are corrupted by the
user program.