Basic programming instructions, Module id codes -3, Basic programming instructions -3 – Rockwell Automation 1746-BAS-T SLC 500 Basic Basic-T Modules User Manual

Page 51: Module id codes

Advertising
background image

Publication 1746-UM004B-EN-P - December 2005

Programming Overview 4-3

Figure 4.2 SLC 5/02 Controller to Module M0 and M1 File Transfer

Module ID Codes

The following table lists the ID codes needed to configure the
memory of your SLC 500 fixed or modular controller.

BASIC Programming
Instructions

BASIC programs are composed of BASIC programming instructions
grouped together. These instructions are a combination of BASIC
commands, statements, operators, and system subroutines (CALLs).

Word 0

Word 1

.

.

.

Word 62

Word 63

Word 100

Word 101

.

.

.

Word 162

Word 163

CPU M0 File

BASIC or

BASIC-T

Module Input

Buffer

Word 0

Word 1

.

.

.

Word 62

Word 63

Word 100

Word 101

.

.

.

Word 162

Word 163

CPU M1 File

BASIC or

BASIC-T

Module Output

Buffer

Controller

Module ID Code

1746-BAS

1746-BAS-T

SLC 500, 5/01

3506

3523 (Class 1)

SLC 5/02 and higher

13106

13123 (Class 4)

IMPORTANT

The module operates in two modes: the Command
mode (Direct mode) and the Run mode (Interpreter
mode). You can only enter commands when the
processor is in the Command mode.