Publication 1746-UM004B-EN-P - December 2005

C-2 Lithium Battery Replacement, Handling, and Disposal

Figure C.1 Battery Location

3. Unplug the battery connector.

4. Remove the battery from the retaining clips.

5. Insert a new battery into the battery retaining clips.

6. Plug the battery connector into the socket with the red lead wire

on top and the white lead wire on the bottom.

7. Re-insert the BASIC module into the SLC 500 chassis.

8. Restore power to the SLC 500 power supply module.

IMPORTANT

The module has a capacitor that provides 30 minutes
of battery back-up while the battery is disconnected.
Data in RAM is not lost if the battery is replaced
within 30 minutes.