Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter

Chapter Summary

In this chapter, you learned how to install and wire your POINT I/O adapter
module. The following chapter describes how to configure your POINT I/O
adapter module to communicate on the EtherNet/IP network by providing an IP
address, gateway address, and Subnet mask.

ATTENTION: Do not wire more than two conductors on any single
terminal.

WARNING: When you connect or disconnect the Removable Terminal
Block (RTB) with field side power applied, an electrical arc can occur.
This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before
proceeding.

WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring
method that complies with the governing electrical codes.

ATTENTION: This product is grounded through the DIN rail to chassis
ground. Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

WARNING: To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with the
following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).