Before you can use your adapter, you must configure its IP address, its subnet
mask, and, optionally, a gateway address. You can use the Rockwell BootP utility,
version 2.3 or later, to perform the

configuration. You can also use a DHCP

server or the network address switches to configure these parameters.

If you need to reset the adapter to factory defaults, see

Work with the

Configuration Pages

in Appendix

B

.

ATTENTION: You must only use Series C and above POINT I/O modules
with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O
modules do not work with 1734-AENT EtherNet/IP Adapters (does not
apply to POINTGuard modules).

IMPORTANT

If you set the thumbwheels on the adapter to the value 888 and then
power cycle the module, the following will occur.

·

The DHCP Enabled function is enabled (set to True).

·

The Ethernet link is negotiated automatically (the Auto Negotiate
function will be set to True).

·

The web server is enabled (the Disabled Web Server function is
disabled).

·

The password for this page resets to the factory default (the word
password is the factory default password).

Note the value of the switches before you enter the 888 value,
because you return the adapter to those values once this process is
complete.