3 outputting analog signals – Rockwell Automation 57C620 AutoMax Programming Executive Version 3.8 User Manual

Page 205

Advertising
background image

18Ć17

On Line Menu: Monitoring and Editing Tasks

18.2.7.2

Modifying Remote I/O Registers

WARNING

THIS FUNCTION MAY BYPASS CONTROL OF THE APPLICATION PROCESS BY

THE APPLICATION TASKS. IT IS THE RESPONSIBILITY OF THE USER TO

DETERMINE THE POTENTIAL HAZARDS INVOLVED. FAILURE TO OBSERVE

THESE PRECAUTIONS COULD RESULT IN BODILY INJURY.

To modify a remote I/O register, follow the directions below.
1. If you have not already done so, enter M" for Modify from the

Monitor I/O menu shown in figure 18.5.

2. Enter R" for Remote" I/O.
3. Enter the slot number of the Remote I/O master module

(M/N 57C416) in the the local rack.

4. Enter the drop number of the remote chassis in which the

module containing the register is located.

5. Enter the slot number of the module in the remote rack that

contains the register.

6. Enter the register number.
7. Enter the desired value of the register. You may enter a decimal

or hexadecimal value only. If you enter a hexadecimal value, the

last character of the value must be the letter H" in upperĆ or

lowerĆcase.

8. Type Enter" or <CR> to write the value to the register.

18.3

Outputting Analog Signals

If your system configuration incorporates a DCS 5000 microĆregulator

drive, the Monitor Analog menu allows you to output two analog

signals that are proportional to the values of the specified integer

variables. These signals can be used to drive a chart recorder,

oscilloscope, or other test instrument. The Monitor Analog is

functional only with a Processor containing a current minor loop

(CML) application task, i.e., a task containing the CML control block.

See JĆ3676 for more information on the Control Block language.
The analog signals are obtained from the the D/A converters located

on the Drive Analog I/O Module (B/M 57405). The variable values are

scaled and updated once every clock tick as long as the CML task is

running. The D/A voltage is:

D/A(volts) = variable * scale *(10 volts/4096 counts)

A maximum of two single precision integer variables can be

displayed simultaneously for each CML task, one per channel. Each

variable is identified by the D/A channel from which the signal is

obtained. The lower channel is identified as 0, and the upper channel

is identified as 1.