5 setup menu – Rockwell Automation 57C620 AutoMax Programming Executive Version 3.8 User Manual

Page 95

Advertising
background image

5Ć39

Using the System Configurator

If any UDC modules exist in the destination rack, you will be

prompted for which operating systems to erase (AutoMax or UDC).

The warning Erase UDC OS before AutoMax OS when erasing all

Processors" will be displayed with the prompt. You can choose to

erase either the OSs on all Processors in the rack or the OS for a

UDC module in the slot you designate. If you want to delete the

operating systems for all AutoMax Processors and UDC modules in

the rack, you must delete the UDC OSs first.

5.4.5

Repairing Databases

In some cases, the Programming Executive will display an error

message which states that the database index files do not match the

database files. This should not occur during normal operation.

Usually, this error occurs if the database files have been changed

without using the Programming Executive or if a Programming

Executive operation was interrupted by turning off the personal

computer. This message will instruct you to use the Repair System

Databases or Repair Rack Databases command. These

commands will reĆindex all index files for the selected system or

selected rack, respectively.

5.5

Setup Menu

The Setup menu is used to modify the Windows configuration and to

set up AutoMax Executive V3.x. You should set up both AutoMax

Executive V3.x and Windows when you install the software.

5.5.1

Modifying the Windows Configuration

Select Windows from the Setup menu to make changes to the

Windows configuration. The Windows Control Panel will be

displayed. See the Microsoft Windows User's Guide for instructions

on using the Windows Control Panel.
Note that in order to print PC tasks (ladder diagrams) and cross

reference files properly, your printer must be capable of printing in

compressed mode (132 columns). You can choose to print in either

landscape or portrait orientation. All printed output will be generated

according to the parameters defined in the Printers setup in

Windows.

5.5.2

Modifying the AutoMax Executive Configuration

with Setup

Select AutoMax from the Setup menu to make changes to the

AutoMax Executive configuration. The Setup dialog box (see

figure 5.16) will display default entries. You can make changes to any

the following fields:

Library Drive Ć Enter the letter of the drive containing the

library you want to work with.
Library Directory Ć The library is the base directory which

will contain the systems you want to work with. The default

library is AMXLIB. You can accept the default or enter the

name of your library directory.

Advertising