Services – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 104

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

96

Services

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

113

Get/Set

Sensor Type

BYTE

Specifies the sensor type.

1 = B TC or 100 Ohm Pt 385
2 = C TC or 200 Ohm Pt 385
3 = E TC
4 = J TC
5 = K TC or 100 Ohm Pt 3916
6 = N TC or 200 Ohm Pt 3916
7 = R TC
8 = S TC
9 = T TC or 10 Ohm Cu 427
10 = 120 Ohm Ni 672 (XM-361
only)
11 = 100 Ohm Ni 618 (XM-361
only)
22 = 250 Ohm Pt 392 (XM-361
only)

116

Get/Set

Digital Filter

UINT

Controls the time
constant of the digital
filter.

Milliseconds

127

Get/Set Channel

ID

(XM-361 only)

CHAR

Channel type identifier
(selects between RTD and
TC options in Sensor
Type
attribute).

B = RTD input
C = TC input

143

Get/Set

Sensor Tag

STRING2

A descriptive name for the
sensor or channel.

147

Get/Set

Data Units

ENGUNIT

The data units of Value,
Low Engineering, and
High Engineering.

Not settable for the XM-361 and
XM-362 modules.

150

Get/Set

Rate Value

REAL

The rate of change of the
analog input value.

Data Units per minute

151

Get/Set

Rate Filter

REAL

Controls the time
constant of the rate filter.

Seconds

Table C.21 Analog Input Point Object Class Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

Table C.22 Analog Input Point Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Class/Instance

Get_Attribute_Single

Returns the contents of the
specified attribute.

10

h

Instance

Set_Attribute_Single

Sets the contents of the
specified attribute.

1

Advertising
This manual is related to the following products: