Mounting the module – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 50

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

42

Mounting the Module

The XM-361 and XM-362 mount on the XM-944 terminal base unit, Cat. No.
1440-TB-E. You should mount the module after you have connected the
wiring on the terminal base unit.

1. Make certain the keyswitch (A) on the terminal base unit (C) is at

position 5 as required for the XM-361 and XM-362 modules.

ATTENTION

The XM-361 and XM-362 are compatible only with the
XM-944 terminal base unit. The keyswitch on the terminal
base unit should be at position 5 for the modules.

Do not attempt to install XM-361 and XM-362
modules on other terminal base units.

Do not change the position of the keyswitch after
wiring the terminal base.

ATTENTION

This module is designed so you can remove and insert it
under power
. However, when you remove or insert the
module with power applied, I/O attached to the module
can change states due to its input/output signal changing
conditions. Take special care when using this feature.

WARNING

When you insert or remove the module while power is on,
an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.

IMPORTANT

Install the overlay slide label to protect serial connector and
electronics when the serial port is not in use.

Advertising