Cos message format – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 85

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

77

COS Message Format

The XM-361 and XM-362 COS message contains nine bytes of data as defined
in the table below. The COS data can also be requested explicitly through
Assembly Object (Class ID 0x4), Instance 100 (0x64), Data Attribute (3).

XM-361/362 Assembly Instance 103 Data Format

Byte

Definition

0–3

Channel 1 measurement value

4–7

Channel 1 rate of change value

8-11

Channel 2 measurement value

12-15

Channel 2 rate of change value

16-19

Channel 3 measurement value

20-23

Channel 3 rate of change value

24-27

Channel 4 measurement value

28-31

Channel 4 rate of change value

32-35

Channel 5 measurement value

36-39

Channel 5 rate of change value

40-43

Channel 6 measurement value

44-47

Channel 6 rate of change value

XM-361/362 COS Message Format

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Relay 1
Status

Reserved

Alarm 2 Status

Alarm 1 Status

1

Relay 2
Status

Reserved

Alarm 4 Status

Alarm 3 Status

2

Relay 3
Status

Reserved

Alarm 6 Status

Alarm 5 Status

3

Relay 4
Status

Reserved

Alarm 8 Status

Alarm 7 Status

4

Relay 5
Status

Reserved

Alarm 10 Status

Alarm 9 Status

5

Relay 6
Status

Reserved

Alarm 12 Status

Alarm 11 Status

6

Relay 7
Status

Reserved

Alarm 14 Status

Alarm 13 Status

7

Relay 8
Status

Reserved

Alarm 16 Status

Alarm 15 Status

8

Reserved

Reserved

Alarm 18 Status

Alarm 17 Status